HIGH PRESSURE PADDLEWHEEL FLOW SENSOR – FLS F3.20
FLS F3.20 is a paddlewheel flow sensor suitable for system at high pressure and at critical temperature. F3.20 is designed for use with every kind of solid-free liquids in compliance with chemical compatibilities of wetted materials. First quality materials used, as SS for body/shaft and Halar® for rotor, grant high mechanical performances and an appreciated reliability. Sensor needs a very limited maintenance and, in those cases, it’s easy to perform due to a 4 screws system and to a graphite flat gasket.F3.20 sensor is available for connection to FLS monitors and for PLC connection directly .SS weld on adapter is available for sensor installation on pipe range from 1 1⁄2” to 8”(DN40 to DN200).
Flow Measurement System

Custom Product Manufacturing Available
If you are searching for customized product designs that meet your requirements, don’t worry. Petron Thermoplast also offers custom product manufacturing services to meet the unique needs of various industries. Work with our expert engineers to create custom designs suited for your application.
APPLICATIONS
• Heat Exchangers
• Reverse osmosis
• Cooling systems
• HVAC systems (heating, ventilation and air conditioning)
• Boiler feedwater
MAIN FEATURES
• Working range up to 110 bar (1600 PSI)and up to 248°F (120 °C)
• Wide operating range (from 0,15 to 8 m/s)
• Just one sensor and one fitting for a wide range of pipe dimensions (from
1 1⁄2” to 8”)
• High linearity and repeatability
• Limited maintanance need and easy execution
• Available special version for direct connection to PLC
Technical Data
General
• Pipe Size Range: DN40 to DN200
(0.5 to 8 in). Refer to Installation Fittings section for
more details
• Flow Rate Range: 0.15 to 8 m/s (0.5 to 25 ft./s)
• Linearity: ± 0.75% of full scale
• Repeatability: ± 0.5% of full scale
• Pressure: 110 bar (1600 psi)
• Temperature: 120 °C (248 °F)
• Minimum Reynolds Number Required: 4500
• Enclosure: IP68
• Wetted Materials:
– sensor Body: 316L SS
– sealing system: graphite flat gasket
– rotor: ECTFE (Halar®)
– shaft: 316L SS
Specific for F3.20.H
• Supply voltage: 5 to 24 VDC regulated
• Supply current: < 30 mA @ 24 VDC
• Output signal:
– square wave
– frequency: 45 Hz per m/s nominal(13.7 Hz per ft/s
nominal)
– output type: transistor NPN open collector
– output current: 10 mA max
• Cable length: 8 m (26.4 ft) standard,300 m (990 ft)
maximum
Specific for F3.20.P
• Supply voltage: 12 to 24 VDC regulated
• Supply current: < 30 mA @ 24 VCC
• Output signal:
– square wave
– output frequency: 45 Hz per m/s nominal (13.7 Hz per
ft/s nominal)
– output type: Push – Pull (digital input NPN or PNP)
– output current: IOut max < 20 mA
• Cable length: 8 m (26.4 ft) standard,300 m (990 ft)
maximum
Standards & Approvals
• Manufactured under ISO 9001
• Manufactured under ISO 14001
• CE
• RoHS Compliant
• EAC
DIMENSIONS
1 Electrical cable: 8 m. (26.4 ft) standard
2 Graphite flat gasket
3 316L SS sensor body
4 ECTFE Halar® Open-cell rotor and
316L SS Shaft
WIRING CONNECTIONS
F3.20.H IP68 Sensor wiring connection
Standards & Approvals
• Manufactured under ISO 9001
• Manufactured under ISO 14001
• CE
• RoHS Compliant
• EAC
DIMENSIONS
1 Electrical cable: 8 m. (26.4 ft) standard
2 Graphite flat gasket
3 316L SS sensor body
4 ECTFE Halar® Open-cell rotor and
316L SS Shaft
Wiring connections to the other monitors
M9.00 | M9.50 | M9.03 | M9.07 | M9.08 | M9.10 | ||
---|---|---|---|---|---|---|---|
GND | 7 | 30 | 30 | 16 | 16 | 16 | 37 |
IN | 8 | 28 | 28 | 14 | 14 | 14 | 36 |
V+ | 9 | 27 | 27 | 13 | 13 | 13 | 35 |
ORDERING DATA
Part No. | Version | Power supply | Length | Main Wetted Materials | Enclosure | Flow Rate Range | Weight |
---|---|---|---|---|---|---|---|
F3.20.H.01 | Hall | 5- 24 VDC | 107 mm | 316L SS | IP 68 | 0.15 to 8 m/s (0.5 to 25 ft./s) | 600 |
F3.20.P.01 | Push-Pull | 12- 24 VDC | 107 mm | 316L SS | IP 68 | 0.15 to 8 m/s (0.5 to 25 ft./s) | 600 |