Dual Parameter Analog Monitor & Transmitter (FLS M9.10) Graphics

DUAL-PARAMETER ANALOG MONITOR & TRANSMITTER - FLS M9.10

The new FLS M9.10 is a powerful monitor and transmitter designed to manage analog and frequency signals (or two analog signals) from every types of device which provide a 4-20mA or a frequency output. M9.10 is equipped with a wide full graphic display 4” which shows measured values clearly and a lot of other useful information. Moreover, due to a multicolor display plus a powerful backlight, measurement status can be determined easily from afar also. A tutorial software guarantees a mistake-proof and fast set up of every parameters. Calibration of 4-20mA input can be performed just fixing 2 points as well as 1 point or using a reference value through a new “in-line calibration”.
Calibration of frequency input can be performed just fixing installation features or using a reference value through a new “in-line calibration”.
Two independent 4-20mA outputs are available to remote measures to external devices. A proper combination of digital outputs (2SSR and 2relays) allows customized setups for any process to be controlled. The USB port on the rear part allows the upgrade of software offering a wide range of customization services both standard and on request.

Key Features of FLS M9.10

Wide graphic display

Multicolor backlight

Help on board

Simultaneous visualization of two parameters

Free setting of engineering unit

Intuitive calibration procedure

In line adjustment

Multilanguage menus

USB port for software upgrading

Technical Information

General

Specification Details
Associated sensors
FLS hall effect flow sensors with frequency output, FLS F6.60 Flow sensor magmeters and all devices which generate a passive or active 4-20mA signal
Materials
case: ABS; display window: PC; panel & wall gasket: silicone rubber; keypad: 5-button silicone rubber
Display
LC full graphic display, backlight version: 3-colours, backlight activation: User adjustable with 5 levels of timing
Update rate
1 second
Enclosure
IP65 front
Frequency input range (frequency)
0÷1000Hz
Frequency accuracy (frequency)
0.5%
Analog input range (frequency)
3.8÷21.0mA
Analog input accuracy (frequency)
0.01mA

Electrical

Parameter Details
Supply Voltage
12 to 24 VDC ± 10% regulated
Max Power Consumption
<300mA
FLS hall effect Flow Sensor power
5 VDC @ < 20 mA
Isolation
Optically isolated from current loop
Short Circuit Protection
Yes
2* Current output
4-20 mA, isolated, fully adjustable and reversible
Max loop impedance
800 Ω @ 24 VDC – 250 Ω @ 12 VDC
Current input power
18VDC @ ≤20mA
2× Solid State Relay output
User selectable as MIN alarm, MAX alarm, Pulse Out (for frequency input), Window alarm, Off
Relay output specs
Optically isolated, 50 mA MAX sink, 24 VDC MAX pull-up voltage; Max pulse/min: 300; Hysteresis: User selectable
2× Relay output
User selectable as MIN alarm, MAX alarm, Pulse Out (for frequency input), Window alarm, Off
Relay contact type
Mechanical SPDT contact
Mechanical life
10⁷ operations
Electrical life
10⁵ N.O./N.C. switching capacity 5A/240VAC
Max pulse/min
60
Hysteresis
User selectable

Standards & Approvals

Certifications Details
Certifications
Manufactured under ISO 9001, Manufactured under ISO 14001, CE, RoHS Compliant, EAC

Environmental

Parameter Details
Operating Temperature
-10 to +70°C (+14 to +158°F)
Storage Temperature
-30 to +80°C (-22 to +176°F)
Relative Humidity
0 to 95% not condensing